Feature | Value |
---|---|
Brand | Remeha |
Supplier Code | 7683599 |
EAN Code | 8713809304454 |
Discount Group | 005 |
Width | 500 mm |
Height | 750 mm |
Depth | 500 mm |
Power Supply | 230 V |
Number of Phases | 1 |
Material Quality | Other |
Flow Connection | External thread |
Return Connection | External thread |
Frequency | 50 Hz |
Connection Voltage | 196 - 253 V |
Closed Construction | Yes |
SEER (Ns) in cooler conditions | 97.4 |
SEER (Ns) in warmer conditions | 88.2 |
Additional Power Consumption at Full Load (ELmax) | 0.114 kW |
Useful Heat Output at Nominal Heat Output and Operation at High Temperature (P4) | 84.2 kW |
Useful Efficiency at Nominal Heat Output and Operation at High Temperature (n4) | 88.2% |
Additional Power Consumption in Standby Mode (Psb) | 0.007 kW |
Standby Heat Loss (Pstby) | 0.123 kW |
Max. Hydrogen Percentage in Mixture with NAT Gas | 20% |
Suitable for Low Calorific Value Natural Gas | Standard Factory Setting |
Suitable for High Calorific Value Natural Gas | Manually Adjustable |
Suitable for Propane | With Conversion Kit, not included |
Suitable for Butane | Not suitable |
Suitable for Methane | Standard Factory Setting |
Suitable for LPG | Not suitable |
Suitable for Hydrogen | Standard Factory Setting |
Heat Exchanger Material | Aluminum |
Integrated Pump Switching | Yes |
Gas Approval VR/SV | No |
Gas Approval NZ | No |
Nominal Load Lower Value | 86 kW |
Nominal Load Upper Value | 92.5 kW |
Min. Operating Pressure | 0.8 bar |
Min. Return Temperature | 20 °C |
Integrated Weather-Dependent Controller | No |
Integrated Expansion Vessel | No |
Hydraulic Resistance at ΔT 20 °C | 15.3 kPa |
Nom. Power 80-60 °C | 84.2 kW |
Max. Flow Temperature (Operating Temperature) | 90 °C |
Integrated Fill/Drain Valve | No |
Integrated Overpressure Valve | No |
External Pipe Diameter Flow | 31.75 mm |
External Pipe Diameter Return | 31.75 mm |
Fuel Connection | External thread |
External Pipe Diameter Fuel | 19.05 mm |
Air Supply Connection | Push-fit |
Nom. Duct Diameter Air Supply | 80 mm |
Flue Gas Connection | Push-fit |
Condensate Connection | Flexible |
External Pipe Diameter Condensate | 25 mm |
Suitable for Natural Gas | Yes |
Gas Approval VR | No |
Nom. Duct Diameter Flue Gas | 100 mm |
Burner Control High/Low | No |
Modulating Burner Control | Yes |
External Pipe Diameter Expansion Connection | 0 mm |
Integrated Manometer | Yes |
Condensing | Yes |
Gas Approval HR | Yes |
Efficiency | 107% |
Pilot Flame | No |
Second Return Connection | No |
Control Signal On/Off | Yes |
Control Signal High/Low | No |
Control Signal 0-10V | Yes |
Control Signal OpenTherm | Yes |
Operation as Open Construction (Air Supply) Possible | Yes |
Nom. Power 50-30 °C | 89.5 kW |
Suitable for Propane | Yes |
Suitable for Butane | No |
Suitable for Methane | Yes |
Max. Allowed Operating Pressure | 4 bar |
Nom. Pipe Diameter Flow | 1 1/4" (32) |
Nom. Pipe Diameter Return | 1 1/4" (32) |
Nom. Pipe Diameter Fuel | 3/4" (20) |
Nom. Pipe Diameter Condensate | DN 25 |
Conversion Kit Required | No |
Gas Approval HR | Yes |
Gas Approval NZ | No |